Cable chauffant ELTRACE

  • Increase font size
  • Default font size
  • Decrease font size
Self Limiting Cable Frost Protection


FROST PROTECTION SELF LIMITING HEATING CABLE TRACECO

E-mail Print PDF

SELF REGULATING HEATING CABLE

Heat tracing TRACECO®

Cable chauffantFrost Protection against ice and low temperature maintenance for Pipe, Tank, Receptacles, valves, gutters…

By using our tracers TRACECO® type, you ensure the best heat-tracing system. They are designed to prevent any risk of burst pipes due to freezing.

Self Limiting or Self Regulating Technology allows easy operation safely. The power changes depending on the temperature and prevents overheating.

When it is cold, the polymer shrinks and facilitates the flow of current, thereby increasing the temperature of the cable. As it gets warmer, the polymer expands and prevents the current: the Self Regulating cable heats less than before.

Finally, a « parallel » technology allows the cable to be cut to desired length directly on the site. Exact fit the length of heating cable for your needs.

The CableBox storage system on coil allows easy handling, quick and convenient. This product is in stock and can be used with the fast connector system DomoClick®

 

Courbe des puissances TRACECO

DESCRIPTION

1. Bus wire Cu nickel-plated (2x1.25mm²)

2. Self limiting heating element

3. Insultation

4. Tin-plated copper protective earth wires with Protective aluminium foil

5. Thermoplastique (TPE-O) outer jacket (Black)

 

 

ATEXCECSTB

 

Last Updated on Tuesday, 03 May 2011 19:39 Read more...
 

SELF LIMITING HEATING CABLE TRACECO®-15

E-mail Print PDF

FROST PROTECTION AGAINST ICE AND LOW TEMPERATURE MAINTENANCE FOR PIPE, TANK, RECEPTACLES, VALVES, GUTTERS…

Self Limiting Cable
By using our tracers TRACECO® type, you ensure the best heat-tracing system. They are designed to prevent any risk of burst pipes due to freezing.
Self Limiting or Self Regulating Technology allows easy operation safely. The power changes depending on the temperature and prevents overheating.  
When it is cold, the polymer shrinks and facilitates the flow of current, thereby increasing the temperature of the cable. As it gets warmer, the polymer expands and prevents the current: the Self Regulating cable heats less than before.
Finally, a « parallel » technology allows the cable to be cut to desired length directly on the site. Exact fit the length of heating cable for your needs.
The CableBox storage system on coil allows easy handling, quick and convenient. This product is in stock and can be used with the fast connector system DomoClick®


HEATING CABLE DESCRIPTIONSELF LIMITING CABLE


Bus wire Cu nickel-plated (2 x 0.55mm²)  
Self limiting heating element
Insultation
Tin-plated copper protective earth wires with Protective aluminium foil
Thermoplastique (TPE-O) outer jacket (Black)

Reference    Désignation    Power    Dimension (naked)    Dimension
TRACECO-15    TRACECO ESR-S-15-AO    12 W/m àat10°C    6,40 x 3,80 (mm)     7,30 x 5,10 (mm)

HEATING CABLE DATASHEET


Nominal Voltage 230V

Maximum length circuit: TRACECO-15…………. 110 m
Tolerances -0/+5 W    
Maximum exposure temperature (energised) 65°C         
Maximum exposure temperature (deenergised) 80°C         
Temperature Class T6                 
Minimum Bending Radius 27 mm                    
Minimum installation temperature -35°C

Weight approx (alufoil) 66 kg/km

Weight approx (Braided) 72 kg/km

CERTIFICATION
CSTB, ATEX, VDE, GOST-R, FIMKO, CE

CIRCUIT LENGTH*


*Maximum Circuit lengths with ELCB curve C
The protection of each circuit shall be in accordance with NF C 15-100.
The protection of persons is ensured by a residual current of 30 mA maximum for each 7.5 kilowatts maximum. The heaters are supplied at 230 volts.

PACKAGING
Standard length on rolls : 500m / CableBox® : 100m

MARQUAGE
Tous les câbles autorégulants ELTRACE sont marqués afin d'assurer la traçabilité du produit.

INSTALLATION
Les câbles autorégulants ELTRACE doivent être installés suivant les normes en vigueur au jour de l’installation (cahier des prescriptions techniques communes de mise en œuvre du CSTB, NF C 15-100, VDE…) pour les points où elles s'appliquent, ainsi que les préconisations d'utilisation.

Last Updated on Tuesday, 03 May 2011 19:41
 

Self Limiting Heating Cable - Corrosive Atmospher, low temperature ESR-BOT

E-mail Print PDF

SELF LIMITING HEATING CABLE

Câble chauffant ELTRACE ESR-BOT

ESR®-BOT

The ESR-BOT tape is a self-limiting heating tape for applications for general protection against freezing in pipes. An additional layer connected to the heating element (bonded jacket) increases the effect of the electrical insulation and provides additional protection against moisture.

Fluoropolymer is used as an outer jacket, this material offers increased protection against chemicals

and abrasion. Fluoropolymers are also UV-resistant.

When it is cold, the polymer shrinks and facilitates the flow of current, thereby increasing the temperature of the cable. As it gets warmer, the polymer expands and prevents the current: the Self Regulating cable heats less than before.

Finally, a « parallel » technology allows the cable to be cut to desired length directly on the site. Exact fit the length of heating cable for your needs.

The CableBox storage system on coil allows easy handling, quick and convenient. This product is in stock and can be used with the fast connector system DomoClick®

DESCRIPTION

Courbe de Puissance des câbles chauffants autorégulants


Bus wire Cu nickel-plated (2x1.25mm²)

Self limiting heating element, Matrix

Insulation

Braid

Fluoropolymer overjacket

Reference    Designation    Power    Dimension

ESR-10-BOT    ESR-2-BOT-10    10 W/m at 10°C    11,50 x 5,50 (mm)

ESR-15-BOT    ESR-2-BOT-15    15 W/m at 10°C    11,50 x 5,50 (mm)

ESR-20-BOT    ESR-2-BOT-20    20 W/m at 10°C    11,50 x 5,50 (mm)

ESR-25-BOT    ESR-2-BOT-25    25 W/m at 10°C    11,50 x 5,50 (mm)

ESR-30-BOT    ESR-2-BOT-33    33 W/m at 10°C    11,50 x 5,50 (mm)


DATASHEET


Nominal Voltage 230V                         Maximum length circuit:

Tolerances -0/+5 W                             ESR-10-BOT…………. 205 m

Maximum exposure temperature (energised) 65°C         ESR-15-BOT…………. 160 m

Maximum exposure temperature (deenergised) 80°C         ESR-20-BOT…………. 140 m

Temperature Class T6 (T5 for 33W/m)                ESR-25-BOT…………. 130 m

Minimum Bending Radius 25 mm                     ESR-30-BOT…………. 110 m

Minimum installation temperature -35°C                 Weight approx 119kg/km


CERTIFICATION

CSTB, ATEX, VDE, GOST-R, CE


CIRCUIT LENGTH*

*Maximum Circuit lengths with ELCB curve C

The protection of each circuit shall be in accordance with NF C 15-100. The protection of persons is ensured by a residual current of 30 mA maximum for each 7.5 kilowatts maximum. The heaters are supplied at 230 volts.


PACKING

Standard length stored on reel: 500m / CableBox® : 100m


PRINTING

All cables are printed in order to ensure the product tracability.


INSTALLATION

ELTRACE self-regulating cables must be installed according to standards prevailing at the date of installation (technical requirements specification for implementation of NF C 15-100, VDE ...) where they apply,


ADDITIONAL PRODUCTS

Last Updated on Tuesday, 03 May 2011 19:43
 

SELF LIMITING HEATING CABLE ESR®-S - Food Compatibility

E-mail Print PDF

SELF LIMITING HEATING CABLE

ESR®-S - Food CompatibilityCable chauffant alimentaire

 

FOR FROST PROTECTION INSIDE PIPE


Self-regulating heating cables ESR-S-BOA have been developed to meet standards
food. You can safely place them inside the pipes. They allow you prevent freezing and the risk of bursting pipes.
The parallel technology "self regulating" allows easy operation safely. Self-regulated power
cable varies with the ambient temperature and prevents overheating. When it's cold
the polymer shrinks and facilitates the flow of current, thereby increasing the temperature cable.
As it gets warmer, the polymer expands and prevents the passage of current: the cable cooler.
Finally,with a technology called "parallel" you can cut the heating cables directly to the desired length on the site, to precisely fit the length of heating cable for your needs.
The storage system on coil type Cablebox ® allows easy handling, quick and convenient.

DESCRIPTION


Bus wire Cu nickel-plated (2 x 0.55mm²)  
Self limiting heating element
Insultation
Tin-plated copper protective earth wires with Protective aluminium foil
Food compatibility outer jacket

Référence    Désignation    Puissance    Section totale
ESR-S-BOA-10    Self Limiting Cable Food Compatibility    10 W/m à 10°C    7,6 x 5,2 (mm)
ESR-S-BOA-15    Self Limiting Cable Food Compatibility    15 W/m à 10°C    7,6 x 5,2 (mm)
ESR-S-BOA-18    Self Limiting Cable Food Compatibility    18 W/m à 10°C    7,6 x 5,2 (mm)

DATASHEET


Nominal Voltage 230V                         Maximum length circuit:
Tolerances -0/+5 W                             ESR-S-BOA-10…………. 100 m
Maximum exposure temperature (energised) 65°C         ESR-S-BOA-15………….   72 m
Maximum exposure temperature (deenergised) 65°C         ESR-S-BOA-18………….   60 m     
Minimum Bending Radius 35 mm
Minimum installation temperature -35°C     

CERTIFICATION

CSTB, ATEX, VDE, GOST-R, FIMKO, CE

CIRCUIT LENGTH*

DESIGNATION      STARTING
TEMPERATURE (°C)      10 A
ESR-S-10-BOA    10°C    100 / 60**
ESR-S-10-BOA    0°C    95
ESR-S-10-BOA    -20°C    77
ESR-S-15-BOA    10°C    72
ESR-S-15-BOA    0°C    66
ESR-S-15-BOA    -20°C    52
ESR-S-18-BOA    10°C    60
ESR-S-18-BOA    0°C    58
ESR-S-18-BOA    -20°C    41
*Maximum Circuit lengths with ELCB curve C
The protection of each circuit shall be in accordance with NF C 15-100.
The protection of persons is ensured by a residual current of 30 mA maximum for each 7.5 kilowatts maximum. The heaters are supplied at 230 volts.

PACKING
Standard length stored on reel: 500m / CableBox® : 100m

PRINTING
All cables are printed in order to ensure the product tracability.

INSTALLATION
ELTRACE self-regulating cables must be installed according to standards prevailing at the date of installation (technical requirements specification for implementation of NF C 15-100, VDE ...) where they apply, and the recommendations of use.

ADDITIONAL PRODUCTS
Reference    Non-ATEX    ATEX
Connexion    Domoclick®  
ELKSR-1, ELKSR    ELKSR-1-e
ELKSR-1-d
Junction Boxes    ELBE-3, ELBE-6, ELBE-8, ELBE-10    ELBA-5-e, ELBA-6-e
ELBA-4-d, ELBA-6-d
Pipe bracket
ELSP-x, ELSP-P1/F, ELSP-P2/F    ELSP-2, ELSP-3, ELSP-4, ELSP-5, ELSP-PU
Thermostats    ELTE-x,
ELTH-A2, ELTH-A3, ELTH-A4    ELTH-Athf-Ex
ELBSTW
Fixing tape    ELAA
ELTV    ELAA
ELTV
Heat Lagging Output    ELSC, ELSC-E    ELSC-E
Adhesive Label    ELET    ELET




CEGOST-R

Last Updated on Tuesday, 03 May 2011 19:45
 

Self Limiting Heating Cable with plug and thermostat

E-mail Print PDF

Self Limiting Heating Cable

GELTRACE®-PROTIGEL

FROST PROTECTING TAPE IS A RELIABLE AND ECONOMICAL SOLUTION TO YOUR PROBLEMS OF FROST PROTECTION

CÂBLE CHAUFFANT GELTRACE PROTIGEL

 

 

Applications:

GELTRACE® range is used for the frost protection of pipes. In the protigel®+ version, the thermostat automatically switches on the tape when the temperature falls under +5°C. It enables substantial energy savings and offers in complement the advantages and the safety of a self-regulating tape.

Avoids drainings and permanent use of hydraulic networks. Easy to implement. Available on stock.

Adjustable length according to the network size. Tape finished and controlled in the factory.

No overheating risk thanks to its self regulating system.

When it is cold, the polymer shrinks and facilitates the flow of current, thereby increasing the temperature of the cable. As it gets warmer, the polymer expands and prevents the current: the Self Regulating cable heats less than before.

Finally, a « parallel » technology allows the cable to be cut to desired length directly on the site. Exact fit the length of heating cable for your needs.

 

Description

1. Bus wire Cu nickel-plated (2 x 0.55mm²)

2. Self limiting heating element

3. Insultation

4. Tin-plated copper protective earth wires with Protective aluminium foil

5. Thermoplastique (TPE-O) outer jacket (Black)

6. Thermostat 5°C

7. Cold lead (1m 3x1.5mm²)

Reference    Designation    Power
GELTRACE-1    Self Limiting cable, 1m lenght, with 5°C thermostat and 1m cold lead    15 W at 10°C
GELTRACE-xx    Self Limiting cable, 1m to 35m lenght, with 5°C thermostat, 1m cold lead    15 W/m at 10°C
GELTRACE-35    Self Limiting cable, 35m lenght, with 5°C thermostat, 1m cold lead    450 W à 10°C

DATASHEET

Nominal Voltage 230V
Maximum length circuit: GELTRACE-35…………. 35 m
Tolérances sur la puissance -0/+5 W
Maximum exposure temperature (energised) 65°C         
Maximum exposure temperature (deenergised) 80°C         
Temperature Class T6                
Minimum Bending Radius 27 mm
Minimum installation temperature -35°C
Weight approx 66 kg/km


QUALIFICATIONS

Certifications CE

CE

 

Last Updated on Tuesday, 03 May 2011 19:47