SELF LIMITING HEATING CABLE
ESR®-S - Food Compatibility
FOR FROST PROTECTION INSIDE PIPE
Self-regulating heating cables ESR-S-BOA have been developed to meet standards
food. You can safely place them inside the pipes. They allow you prevent freezing and the risk of bursting pipes.
The parallel technology "self regulating" allows easy operation safely. Self-regulated power
cable varies with the ambient temperature and prevents overheating. When it's cold
the polymer shrinks and facilitates the flow of current, thereby increasing the temperature cable.
As it gets warmer, the polymer expands and prevents the passage of current: the cable cooler.
Finally,with a technology called "parallel" you can cut the heating cables directly to the desired length on the site, to precisely fit the length of heating cable for your needs.
The storage system on coil type Cablebox ® allows easy handling, quick and convenient.
DESCRIPTION
Bus wire Cu nickel-plated (2 x 0.55mm²)
Self limiting heating element
Insultation
Tin-plated copper protective earth wires with Protective aluminium foil
Food compatibility outer jacket
Référence Désignation Puissance Section totale
ESR-S-BOA-10 Self Limiting Cable Food Compatibility 10 W/m à 10°C 7,6 x 5,2 (mm)
ESR-S-BOA-15 Self Limiting Cable Food Compatibility 15 W/m à 10°C 7,6 x 5,2 (mm)
ESR-S-BOA-18 Self Limiting Cable Food Compatibility 18 W/m à 10°C 7,6 x 5,2 (mm)
DATASHEET
Nominal Voltage 230V Maximum length circuit:
Tolerances -0/+5 W ESR-S-BOA-10…………. 100 m
Maximum exposure temperature (energised) 65°C ESR-S-BOA-15…………. 72 m
Maximum exposure temperature (deenergised) 65°C ESR-S-BOA-18…………. 60 m
Minimum Bending Radius 35 mm
Minimum installation temperature -35°C
CERTIFICATION
CSTB, ATEX, VDE, GOST-R, FIMKO, CE
CIRCUIT LENGTH*
DESIGNATION STARTING
TEMPERATURE (°C) 10 A
ESR-S-10-BOA 10°C 100 / 60**
ESR-S-10-BOA 0°C 95
ESR-S-10-BOA -20°C 77
ESR-S-15-BOA 10°C 72
ESR-S-15-BOA 0°C 66
ESR-S-15-BOA -20°C 52
ESR-S-18-BOA 10°C 60
ESR-S-18-BOA 0°C 58
ESR-S-18-BOA -20°C 41
*Maximum Circuit lengths with ELCB curve C
The protection of each circuit shall be in accordance with NF C 15-100.
The protection of persons is ensured by a residual current of 30 mA maximum for each 7.5 kilowatts maximum. The heaters are supplied at 230 volts.
PACKING
Standard length stored on reel: 500m / CableBox® : 100m
PRINTING
All cables are printed in order to ensure the product tracability.
INSTALLATION
ELTRACE self-regulating cables must be installed according to standards prevailing at the date of installation (technical requirements specification for implementation of NF C 15-100, VDE ...) where they apply, and the recommendations of use.
ADDITIONAL PRODUCTS
Reference Non-ATEX ATEX
Connexion Domoclick®
ELKSR-1, ELKSR ELKSR-1-e
ELKSR-1-d
Junction Boxes ELBE-3, ELBE-6, ELBE-8, ELBE-10 ELBA-5-e, ELBA-6-e
ELBA-4-d, ELBA-6-d
Pipe bracket
ELSP-x, ELSP-P1/F, ELSP-P2/F ELSP-2, ELSP-3, ELSP-4, ELSP-5, ELSP-PU
Thermostats ELTE-x,
ELTH-A2, ELTH-A3, ELTH-A4 ELTH-Athf-Ex
ELBSTW
Fixing tape ELAA
ELTV ELAA
ELTV
Heat Lagging Output ELSC, ELSC-E ELSC-E
Adhesive Label ELET ELET


| < Prev | Next > |
|---|