| Power regulator Therm-Control |
|
|
Power controller for heating tapes DHB-330 |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Adjustment range | 35 to 70°C |
| Service voltage | 230 V ~+10 / -15 % |
Mains frequency | 50 Hz |
| Cut-off amperage | 13 A |
Consumption | 3 VA |
Protection class (1) | IP 20 |
Admissible ambient temperature | -10 to +50°C |
Timer working reserve | 12 h |
Dimensions | 90 x 71 x 58 mm |
Weight | 0.25 kg |
Fixing | on DIN rail in distribution cabinet |
Max length of TRACECO®W-55 | 120 m |
Max length of TRACECO®W-65 | 100 m |
| Adjustment range | 35 to 70°C |
| Service voltage | 230 V ~+10 / -15 % |
| Mains frequency | 50 Hz |
| Cut-off amperage | 13 A |
| Consumption | 3 VA |
| Protection class (1) | IP 20 |
| Admissible ambient temperature | -10 to +50°C |
| Timer working reserve | 12 h |
| Dimensions | 90 x 71 x 58 mm |
| Weight | 0.25 kg |
| Fixing | on DIN rail in distribution cabinet |
| Max length of TRACECO®W-55 | 120 m |
| Max length of TRACECO®W-65 | 100 m |
| Adjustment range | 35 to 70°C |
| Service voltage | 230 V ~+10 / -15 % |
| Mains frequency | 50 Hz |
| Cut-off amperage | 13 A |
| Consumption | 3 VA |
| Protection class (1) | IP 20 |
| Admissible ambient temperature | -10 to +50°C |
| Timer working reserve | 12 h |
| Dimensions | 90 x 71 x 58 mm |
| Weight | 0.25 kg |
| Fixing | on DIN rail in distribution cabinet |
| Max length of TRACECO®W-55 | 120 m |
| Max length of TRACECO®W-65 | 100 m |
n Warranty
For a guarantee of perfect working, it is essential to use only Eltrace heating tapes. Eltrace SAS declines any liability when Therm-Control is used with other bands.n Accessories
- DKS 901 Box for visible assembly IP 30.
- DKS 902 Dust and water proof box IP 55.
- DMI 512 Lock for box DKS 902.
n Electrical connections
- Connection to the mains by live, neutral and earth. Heating tape to live, neutral and earth. Temperature probe at the TT terminals.
- Service Instructions for Therm-Control, type DHB 330 FPower controller for Eltrace heating tape
Function
Therm-Control is an electronic device for adjusting Eltrace heating tape.
Power Regulator
The maintained temperature required at the heating tape can be chosen, and therefore the surface area of the pipes, within a range of 35 to 59°C (Hb 60), 35 to 72°C (Hb 70) and 35 to 58°C (Hb 55) (factory adjustment Hb 60, 59°C).
Disinfection
Once each week for 6 hours, it may be necessary to set the heating tape to maximum temperature. The day of the week is set on the switching clock at the "disinfection" level. Disinfection will then begin automatically on night service changeover.
Switching clock
The clock integrated into the regulator makes it possible to interrupt the operation of the heating tape once every 24 hours. If this function is not used, leave the setting on 00.00, both for starting and stopping times.The clock has an operating capability of 12 h.
Starting current limiter
The consumption of current by heating tape depends essentially on the surface temperature of the pipe and on ambient temperature. When the tapes are cold, in order not to draw excessively on the network, DHB 330, for a maximum of 8 minutes after each startup, limits the quantity of current consumed. Adjustment is then free.
Technical data
Adjustment range:
Hb 60: 35 to 59°C (factory adjustment)
Hb 70: 36 to 72°C
Hb 55: 35 to 58°C
Operating voltage
230 V~ +10 to -15%
Network frequency 50 Hz
Breaking capacity 13 A
Consumption 3 VA
Clock operating reserve 12 h
Protection class IP 20
Permissible ambient temperature - 10 to 50°C
Size : 90 x 71 x 58 mm
Symbole = Switching clock
°C = DisinfectionIn service, the display indicates the maintenance temperature
Adjustments
Set point value programming Hold the "mode" key down and briefly, during the second that follows, press the "set" key. The display 00.00 flashes. The equipment is ready for programming.To modify the setpoint values, press briefly the "set" button as many times as necessary. By pressing the "set" button slightly longer, the figures will scroll faster. To change parameter, press the "mode" button briefly.¯ Hold the "mode" button down and briefly operate the "set" key during the second that follows.Heating tape active, LED $ lights up!® Press the "set" key until the desired time is displayed.(Default value = 00.00; changes in one quarter hour steps).¯ Press briefly the "mode" button.Heating tape inactive, LED $ lights up!® Press the "set" key until the desired time is displayed.(Default value = 00.00; changes in quarter hour steps)¯ Press briefly on the "mode" button.Type of heating tape, LED $ lights up!® Press the "set" button until the type of heating tape desired is displayed.
Hb 60 =ESR-W-55-BO
Hb 70 = ESR-W-65-BO
Hb 55 =ESR-30-BO
(Default value = Hb 60; selection Hb 70 or Hb 55 possible)
¯ Press briefly the "mode" button.Desired holding temperature, LED °C lights up
!® Press the "set" button until the desired temperature is displayed.(Default value 59°C (Hb 60); changes in steps of 1°C.¯ Press briefly the "mode" button.Disinfection, LED °C lights !(Default value Hy0 = off; Hy1 to Hy7 = Monday to Sunday)Size 90 x 71 x 58 mm
Weight 0.25 kg
Mounting on DIN rail in distribution cabinetCE1) Depends on type of heating tape DHB 200/B = 100 m/13(10)ADHB 201/B = 80 m/13(10)A Fault current circuit-breakers (FI)The heating tape must be protected by a 300 mA fault current circuit-breaker. Electrical connection
The performance of al the connecting and maintenance works will be entrusted exclusively to an authorized electrician.Before working on live equipment, be sure to connect the power outlet from the mains. Connection to mains by terminals L1, N and by grounding.Heating tape across terminals NN, LL and ground.
Display
The display shows setpoint values and effective values while LEDs indicate the functions to which they refer.
Function
LED$ = Active heating tape = LED on
Starting current limiter active = LED flashing$ = Active heating tape (day)$ = Inactive heating tape (night)°C = Maintenance temperature (Sunday).¯ Press briefly the "mode" buttonUpdating the day of the week, LED $ lights up!(Default value d1 = Monday; d1 to d7 = Monday to Sunday)¯ Press briefly the "mode" button.Current time setting, LED $ lights up® Press the "set" button until the current time is displayed.(Default value 06.00, changes in 1 min. steps). By pressing the "set" button longer, the displayed time will change quickly. Recording of program setpoint valuesPress simultaneously on the "mode" and "set" buttons until the display indicates (---).If none of the buttons is pressed for a period of 3 min., the programming mode will be abandoned automatically and no value will be recorded! Modification of setpoint valuesSee "Programming of setpoint values" above. Operating testsTo perform these tests, it is possible to manual start or stop the heating tape. Press the "set" button for 2 seconds. The heating tape is then activated. The indicator light displays tESt. The LED $ flashes during the time the starting current limiter is operating. Then the LED $ remains on. By pressing the "set" button again, the heating tape is deactivated/activated. When manual mode is not canceled, the system itself, after 15 minutes, returns to the normal programmed mode. Operating guarantee / Civil responsibility Eltrace declines any responsibility in the event of heating tape from other origins being used.