Frost-Control Thermostat in cabinets Thermostat for heating tapes. Therm-Control is an electronic appliance for adjusting Eltrace heating tapes for pipes liable to freeze.
Thermostat” featureThe thermostat allows adjustment from -5 to +70°C The heating tape is switched on below the programmed temperature and shut off above it. The recommended order value (factory set) is +3°C. “Start-up current limiter” featureCurrent consumption by the heating tapes essentially depends on the pipe surface temperature and the ambient temperature. When the bands are cold, so as not to overload the mains, the DHB 340 limits the quantity of absorbed current for a maximum of 8 min. according to each switching on. The adjustment is then free. “Display” featureThe display shows the effective order values, whilst the small LED’s signal the features to which they refer. In service, the display indicates the measured temperature, for example: 3°C. Error messageE1 = Sensor failure (interruption/short-circuit). For safety questions, the appliance switches to permanent working mode! Installing the temperature sensorThe sensor can be used, at will, to measure the ambient temperature or that of the pipe surface. In the latter case, it should be fixed on the opposite side to that of the heating tape, by imperatively choosing the coldest part of the whole installation.
Technical Data: Adjustment range -5 to +70 °C Kicking-in differential +/- 0,5 K. Service voltage 230 V ~ +10 / -15 Mains frequency 50 Hz Cut-off amperage 13 A Consumption 3 VA Protection class (1) IP 20 Admissible ambient temperature (thermostat) -10 to +50 °C Sensor type NTC Sensor cable length 5 m Maximum probe cable length Ø 1 mm 50 m (2) Admissible ambient temperature (probe) -20 to +80 °C Dimensions 90 x 71 x 58 mm Weight 0.25 kg Fixing on DIN rail in distribution cabinet
Maximum length TRACECO®-10: 170 m TRACECO®-20: 120 m TRACECO®-W-55: 120 m n WarrantyFor a guarantee of perfect working, it is essential to use only Eltrace heating tapes. Eltrace SAS declines any liability when Frost-Control is used with other bands. n AccessoriesDKS 901 Box for visible assembly IP 30. DKS 902 Dust and water proof box IP 55. DMI 512 Lock for box DKS 902. n Electrical connectionsConnection to the mains by live, neutral and earth. Heating tape to live, neutral and earth. Temperature probe at the TT terminals. n Dimensions DHB 340 DKS 901 DKS 902 |